Component guide · Intermediate · 4 min read
RS485 to 4G MQTT Gateways

Wittelb WIN-GW, Waveshare, Calixto and Teltonika TRB
By Geekobot Learning Team · Updated 29 Oct 2026
On this page
An RS485 to 4G gateway reads Modbus devices such as energy meters, flow meters and PLCs, and sends the data to a cloud server over a SIM card. Some, like the Waveshare DTU, simply tunnel serial data to a TCP server; others, like the Wittelb WIN-GW and Teltonika TRB145, poll Modbus registers themselves and publish values as MQTT or HTTP. That makes remote monitoring possible where there is no Wi-Fi or LAN.
Key specs at a glance
- Network
- 4G LTE Cat 1 or Cat 4 (check Indian bands B1/B3/B5/B8/B40/B41)
- Serial
- RS485 (TRB246 and some others also RS232)
- Protocols
- Transparent TCP/UDP, Modbus RTU master, MQTT, HTTP
- Extras
- Ethernet, digital and analog IO on some models
- Supply
- 9 to 36 V DC typical
- Mounting
- DIN rail or wall
Models in this guide
These are alternatives. Pick the one that fits your project; you only need one.
Option 1Wittelb WIN-GW-4G+RS485 MQTT IoT Gateway₹5,444
Option 2Wittelb WIN-GW 4G + RS485 + Ethernet IoT Gateway₹6,111
Option 3Wittelb RS485 to 4G MQTT IoT Gateway w/ Built-in IO₹11,668
Option 4Wittelb WIN-GW-4G+IO (4DDAM)+ETH RS485 to 4G MQTT Ethernet IoT Gateway₹10,333
Option 5Waveshare Industrial 4G RS485 to LTE Cat4 DIN Rail Gateway (EU)₹9,659
Option 6Calixto MBGWY00x Modbus to Cloud Gateway w/ RS485 & 4G₹7,000
What the RS485 to 4G MQTT gateway is
There are two styles. A DTU (data transfer unit) sends raw serial bytes to a server, which then has to speak Modbus itself. A Modbus gateway does the polling locally: you list the slave address, function code, register and interval, and it sends the values as JSON to an MQTT broker.
Teltonika TRB gateways run RutOS with a full web interface, VPN and remote management. Wittelb and Calixto gateways are built for Indian SIMs and cloud dashboards.
RS485 to 4G MQTT gateway pinout
The pins on the RS485 to 4G MQTT gateway and what each one does.
| Pin | Function |
|---|---|
| A+ / B- / GND | RS485 bus |
| SIM slot | Micro or nano SIM with data |
| LTE antenna | SMA, one or two (main and diversity) |
| LAN | Ethernet on some models |
| DI / DO / AI | Built-in IO on IO models |
| Power | 9 to 36 V DC |
- A+ / B- / GND
- RS485 bus
- SIM slot
- Micro or nano SIM with data
- LTE antenna
- SMA, one or two (main and diversity)
- LAN
- Ethernet on some models
- DI / DO / AI
- Built-in IO on IO models
- Power
- 9 to 36 V DC
Wiring the RS485 to 4G MQTT gateway
Metal panels block 4G; run the antenna outside the enclosure. Check the slave address, baud rate and parity of every device before configuring polling.
| RS485 to 4G MQTT gateway pin | Gateway | Notes |
|---|---|---|
| A+ / B- | Meter or PLC RS485 | - |
| Power | 12 or 24 V supply | - |
| Antenna | LTE antenna outside the panel | - |
| SIM | Data SIM, PIN disabled | - |
- A+ / B-
- Gateway:
- Meter or PLC RS485
- Notes:
- -
- Power
- Gateway:
- 12 or 24 V supply
- Notes:
- -
- Antenna
- Gateway:
- LTE antenna outside the panel
- Notes:
- -
- SIM
- Gateway:
- Data SIM, PIN disabled
- Notes:
- -
Example code
Field names differ by brand, but every Modbus to MQTT gateway asks for these values. Subscribe to the topic in Node-RED, Home Assistant or your cloud dashboard to see the data.
Serial: 9600 baud, 8N1
Poll 1: slave 1, function 03, start 0, count 2, every 60 s (meter voltage)
Poll 2: slave 1, function 03, start 6, count 2, every 60 s (meter power)
MQTT: broker mqtt.example.in, port 1883, client ID site-01
Topic: site-01/meter1
Payload: {"voltage": 231.4, "power": 1520}Setup and tuning
use a data plan on a network with good signal at the site; IoT SIMs with static IPs help for remote access.
set the APN for your operator in the gateway's mobile settings.
do not poll faster than you need; data costs and bus load add up.
use MQTT over TLS or a VPN, and change default web passwords.
run A, B and a ground or shield wire; A to A and B to B on every device.
fit 120 ohm resistors only at the two ends of a long bus.
daisy-chain the devices; avoid stars and long stubs.
every device on one bus needs the same baud rate and parity and a unique Modbus address.
What you need
Shop this list12 of 12 found in our store · ₹86,364
Wittelb WIN-GW-4G+RS485 MQTT IoT Gateway: the part this guide coversWittelb WIN-GW-4G+RS485 MQTT IoT Gateway₹5,444
Wittelb WIN-GW 4G + RS485 + Ethernet IoT Gateway: another version this guide coversWittelb WIN-GW 4G + RS485 + Ethernet IoT Gateway₹6,111
Wittelb RS485 to 4G MQTT IoT Gateway w/ Built-in IO: another version this guide coversWittelb RS485 to 4G MQTT IoT Gateway w/ Built-in IO₹11,668
Wittelb WIN-GW-4G+IO (4DDAM)+ETH RS485 to 4G MQTT Ethernet IoT Gateway: another version this guide coversWittelb WIN-GW-4G+IO (4DDAM)+ETH RS485 to 4G MQTT Ethernet IoT Gateway₹10,333
Waveshare Industrial 4G RS485 to LTE Cat4 DIN Rail Gateway (EU): another version this guide coversWaveshare Industrial 4G RS485 to LTE Cat4 DIN Rail Gateway (EU)₹9,659
Calixto MBGWY00x Modbus to Cloud Gateway w/ RS485 & 4G: another version this guide coversCalixto MBGWY00x Modbus to Cloud Gateway w/ RS485 & 4G₹7,000
Teltonika TRB145 Industrial RS485 LTE Gateway: another version this guide coversTeltonika TRB145 Industrial RS485 LTE Gateway₹14,969
Teltonika TRB246 Industrial LTE Gateway w/ RS232 & RS485: another version this guide coversTeltonika TRB246 Industrial LTE Gateway w/ RS232 & RS485₹20,629
24V 4A switching power supply board: the usual supply for DIN rail devices24V 4A AC-DC Switching Power Supply Board₹411Closest match, check the specs
USB to RS485 converter adapter: to test the bus from a PCUSB to RS485 Converter Adapter₹74
DIN rail screw terminal block: to land field wires neatly on the railDIN Rail Screw Terminal Block₹20
GSM antenna with 1 m cable and SMA plug: an antenna to fit outside a metal panelGSM Antenna SMA 5cm 900-1800MHz 2dBi₹46Closest match, check the specs
Alternatives and when to choose them
- Industrial 4G routers: internet for a whole panel, some with RS485.
- RS485 to Ethernet serial servers: same job over LAN.
- MQTT with Home Assistant: where the MQTT data can land.
Common mistakes to avoid
- Antenna inside a closed metal panel.
- Wrong APN, so data never connects.
- Polling a register map from a different meter model.
- Leaving default passwords on a gateway with a public IP.
Frequently asked questions
DTU or Modbus gateway?
A Modbus gateway for dashboards and MQTT; a DTU when your server already speaks Modbus.
Which SIM works?
Any 4G data SIM on supported bands; Airtel, Jio and Vi all work on Cat 1 and Cat 4 modules with Indian bands.
How much data does it use?
A few MB a month for readings every minute.
Can I configure it remotely?
Teltonika RMS and some maker clouds allow remote configuration.
Does it need a PC on site?
No. The gateway runs on its own once configured.
Parts for this guide
Keep learning
Sources
Written by the Geekobot team from manufacturer datasheets. Always check the datasheet for the exact part and variant you buy.