Component guide · Intermediate · 3 min read
RS485 Modbus Microwave and Dual-Technology

PIR plus Microwave) Presence Detectors
By Geekobot Learning Team · Updated 29 Oct 2026
On this page
These ceiling detectors report presence over RS485 Modbus RTU, so a PLC, gateway or ESP32 can read many of them on one cable. The Renke unit uses 24 GHz radar; the dual-technology alarm combines PIR and microwave and only triggers when both agree, which cuts false alarms. They run from 10 to 30 V DC and use standard Modbus holding registers.
Key specs at a glance
- Supply
- About 10 to 30 V DC
- Interface
- RS485 Modbus RTU
- Default
- Usually address 1, 9600 baud (check manual)
- Sensing
- 24 GHz radar or PIR plus microwave
- Mounting
- Ceiling
- Cable
- Up to hundreds of metres of twisted pair
Models in this guide
These are alternatives. Pick the one that fits your project; you only need one.
What the RS485 microwave and dual-tech presence detectors is
RS485 microwave presence detectors are radar sensors that report presence, motion and distance over Modbus, used in building automation and lighting control.
Modbus lets you put many sensors on one pair of wires, each with its own address. Change the address of each unit before connecting them together.
Dual-technology detectors need both PIR and microwave to agree, which suits alarms where false triggers are costly.
RS485 microwave and dual-tech presence detectors pinout
The pins on the RS485 microwave and dual-tech presence detectors and what each one does.
| Pin | Function |
|---|---|
| V+ | 10 to 30 V DC |
| GND | Ground |
| A+ | RS485 A |
| B- | RS485 B |
- V+
- 10 to 30 V DC
- GND
- Ground
- A+
- RS485 A
- B-
- RS485 B
Wiring the RS485 microwave and dual-tech presence detectors
Connect the RS485 microwave and dual-tech presence detectors like this.
| RS485 microwave and dual-tech presence detectors pin | Arduino Uno | ESP32 |
|---|---|---|
| V+ (red/brown) | 12 V supply + | 12 V supply + |
| V- / GND (black) | Supply - and board GND | Supply - and board GND |
| A+ (yellow) | MAX485 A | MAX485 A |
| B- (white/blue) | MAX485 B | MAX485 B |
| MAX485 RO / DI | D10 / D11 (SoftwareSerial) | GPIO 16 / GPIO 17 |
| MAX485 DE+RE | D4 | GPIO 4 |
- V+ (red/brown)
- Arduino Uno:
- 12 V supply +
- ESP32:
- 12 V supply +
- V- / GND (black)
- Arduino Uno:
- Supply - and board GND
- ESP32:
- Supply - and board GND
- A+ (yellow)
- Arduino Uno:
- MAX485 A
- ESP32:
- MAX485 A
- B- (white/blue)
- Arduino Uno:
- MAX485 B
- ESP32:
- MAX485 B
- MAX485 RO / DI
- Arduino Uno:
- D10 / D11 (SoftwareSerial)
- ESP32:
- GPIO 16 / GPIO 17
- MAX485 DE+RE
- Arduino Uno:
- D4
- ESP32:
- GPIO 4
Example code
Register numbers vary by maker; read the manual for which register holds the presence state.
// Read an RS485 Modbus RTU sensor with a MAX485 module (ModbusMaster library)
#include <ModbusMaster.h>
const int DE_RE = 4; // tie DE and RE together
ModbusMaster node;
void preTx() { digitalWrite(DE_RE, HIGH); }
void postTx() { digitalWrite(DE_RE, LOW); }
void setup() {
Serial.begin(115200);
Serial2.begin(9600, SERIAL_8N1, 16, 17);
pinMode(DE_RE, OUTPUT); postTx();
node.begin(1, Serial2); // slave address 1 (check the manual)
node.preTransmission(preTx);
node.postTransmission(postTx);
}
void loop() {
if (node.readHoldingRegisters(0x0000, 2) == node.ku8MBSuccess) {
Serial.print("Reg 0: "); Serial.print(node.getResponseBuffer(0));
Serial.print(" Reg 1: "); Serial.println(node.getResponseBuffer(1));
} else {
Serial.println("No reply - check A/B, address and baud");
}
delay(1000);
}Setup and tuning
typically 12 to 24 V DC.
A and B on twisted pair; terminate the ends of the bus.
set Modbus address, baud rate, range and sensitivity registers.
ceiling or wall, away from fans and moving machinery.
read presence registers from a PLC or BMS.
What you need
Shop this list6 of 6 found in our store · ₹5,594
Renke RS-HWB-N01-3 PIR Motion Sensor – 24.00~24.25GHz Ceiling Mount, RS485 Modbus-RTU: the part this guide coversRenke RS-HWB-N01-3 PIR Motion Sensor – 24.00~24.25GHz Ceiling Mount, RS485 Modbus-RTU₹3,139
SN-300XD2-HWB-N01 Infrared Microwave Dual Detection Alarm (RS485 Modbus): another version this guide coversSN-300XD2-HWB-N01 Infrared Microwave Dual Detection Alarm (RS485 Modbus)₹1,667
MAX485 RS-485 to TTL module: to read RS485 versions from a microcontrollerMAX485 RS-485 to TTL Module₹28
USB to RS485 converter adapter: to test RS485 versions from a PCUSB to RS485 Converter Adapter₹74
SMPS power supply in metal enclosure (5/12/24 V): a 12 V or 24 V supplySMPS Power Supply, Metal Enclosure (5V / 12V / 24V)₹298Closest match, check the specs
ESP32-WROOM-32 38-pin development board: for Wi-Fi logging and dashboardsESP32-WROOM-32 38-Pin Development Board₹389
Alternatives and when to choose them
- Modbus RTU with Arduino and ESP32: how to read any Modbus sensor.
- LD2410 presence radar: low-cost UART alternative.
- RS485 to Ethernet: to bring the bus onto a network.
Common mistakes to avoid
- Duplicate addresses.
- Facing moving machinery.
- No bus termination.
- Sensitivity too high.
Frequently asked questions
How do presence detectors differ from motion detectors?
They detect tiny breathing motions, so still people are still detected.
How do I read it with a PLC?
Read the presence and distance registers over Modbus RTU from the PLC's RS485 port.
Why does it detect presence in an empty room?
Fans or vibration are moving in range; lower the sensitivity or shorten the range.
Can I connect several detectors on one bus?
Yes. Give each detector a unique Modbus address on the same bus.
Can it see through glass?
Yes, radar passes glass, which can cause detections in the next room.
Parts for this guide
Keep learning
Sources
Written by the Geekobot team from manufacturer datasheets. Always check the datasheet for the exact part and variant you buy.