These are ready-made sensors for buildings, factories and kitchens. The PM transmitters hold a laser sensor in a wall box and report PM2.5 and PM10 over RS485 Modbus RTU, with 4-20 mA or 0-10 V options on some. The smoke sensors are photoelectric detectors that report an alarm register over Modbus. The Tuya unit is a battery smoke alarm that alerts your phone over Wi-Fi.
Key specs at a glance
- Supply
- 10-30V DC typical for RS485 models
- Bus
- RS485 Modbus RTU, 4800 or 9600 baud default
- PM range
- 0-1000 or 0-2000 µg/m³
- Analog
- 4-20 mA, 0-5V or 0-10V on some PM models
- Smoke
- Photoelectric, alarm register 0 or 1
- Tuya
- 2.4 GHz Wi-Fi, AAA batteries, app alerts
Models in this guide
These are alternatives. Pick the one that fits your project; you only need one.
Option 1Renke RS-PM-N01-2 Air Quality PM2.5 PM10 Sensor – RS485/0-5V/0-10V/4-20mA Output₹7,169
Option 2SN-3002-PM-N01 (485) Air Quality Detector Sensor, Wall-Mount, 0-2000 µg/m³ Range – RS485/4-20mA/0-10V Output₹3,779
Option 3Wittelb WIN-SN-PM2.5/1/10-M Particulate Matter Sensor – Modbus RS485, 12-24V DC₹6,948
Option 4Wittelb WIN-SN-PM2.5/1/10-M-D Particulate Matter Sensor with Display – RS485 Modbus₹7,075
Option 5Renke RS-YG-N01 RS485 Photoelectric Smoke Sensor – Modbus-RTU, 10-30V DC₹7,179
Option 6SN-3000-YG2-N01 Smoke Sensor – RS485 Modbus-RTU, 12/24V DC₹6,089
What the RS485 Modbus PM2.5 transmitters and smoke sensors (Renke, Wittelb, SN-3000 and JXBS) is
RS485 PM and smoke sensors measure PM2.5, PM10 or smoke density and report it over Modbus RTU for weather stations, factories and building monitoring.
Read the label for the default slave address and baud rate, usually address 1 at 4800 or 9600 baud. PM transmitters return PM2.5 and PM10 as plain integers in µg/m³ from holding registers starting at 0. Wire several on one bus after giving each a different address.
The oil smoke sensor suits kitchen exhausts. RS485 smoke sensors are for monitoring and automation, not a replacement for a certified fire alarm system. Use a PLC, an RS485 gateway or an ESP32 with a MAX485 board to collect readings.
RS485 Modbus PM2.5 transmitters and smoke sensors (Renke, Wittelb, SN-3000 and JXBS) pinout
The pins on the RS485 Modbus PM2.5 transmitters and smoke sensors (Renke, Wittelb, SN-3000 and JXBS) and what each one does.
| Pin | Function |
|---|---|
| Brown / red | 10-30V DC + |
| Black | GND |
| Yellow / green | RS485 A+ |
| Blue / white | RS485 B- |
| 4-20 mA | Analog output on some |
- Brown / red
- 10-30V DC +
- Black
- GND
- Yellow / green
- RS485 A+
- Blue / white
- RS485 B-
- 4-20 mA
- Analog output on some
Wiring the RS485 Modbus PM2.5 transmitters and smoke sensors (Renke, Wittelb, SN-3000 and JXBS)
Wire colours vary by maker; follow the label on the cable.
| RS485 Modbus PM2.5 transmitters and smoke sensors (Renke, Wittelb, SN-3000 and JXBS) pin | Connection | Note |
|---|---|---|
| V+ | 12 or 24V DC supply | Common ground with the reader |
| A+ | Converter A or D+ | Twisted pair |
| B- | Converter B or D- | 120Ω at bus ends |
- V+
- Connection:
- 12 or 24V DC supply
- Note:
- Common ground with the reader
- A+
- Connection:
- Converter A or D+
- Note:
- Twisted pair
- B-
- Connection:
- Converter B or D-
- Note:
- 120Ω at bus ends
Example code
Register addresses differ by model; confirm them in the manual before use.
import minimalmodbus, time
s = minimalmodbus.Instrument("/dev/ttyUSB0", 1) # port, slave address
s.serial.baudrate = 4800 # check the label
s.serial.timeout = 1
while True:
pm25 = s.read_register(0, 0, functioncode=3)
pm10 = s.read_register(1, 0, functioncode=3)
print(f"PM2.5 {pm25} PM10 {pm10} ug/m3")
time.sleep(5)Setup and tuning
usually 10 to 30 V DC.
connect A and B to the RS485 bus with shielded twisted pair.
set address and baud rate; read PM registers.
mount outdoors in a shelter or indoors away from vents and cooking.
clean inlets regularly.
What you need
Shop this list8 of 9 found in our store · ₹43,577
Renke RS-PM-N01-2 Air Quality PM2.5 PM10 Sensor – RS485/0-5V/0-10V/4-20mA Output: the part this guide coversRenke RS-PM-N01-2 Air Quality PM2.5 PM10 Sensor – RS485/0-5V/0-10V/4-20mA Output₹7,169
SN-3002-PM-N01 (485) Air Quality Detector Sensor, Wall-Mount, 0-2000 µg/m³ Range – RS485/4-20mA/0-10V Output: another version this guide coversSN-3002-PM-N01 (485) Air Quality Detector Sensor, Wall-Mount, 0-2000 µg/m³ Range – RS485/4-20mA/0-10V Output₹3,779
Wittelb WIN-SN-PM2.5/1/10-M Particulate Matter Sensor – Modbus RS485, 12-24V DC: another version this guide coversWittelb WIN-SN-PM2.5/1/10-M Particulate Matter Sensor – Modbus RS485, 12-24V DC₹6,948
Wittelb WIN-SN-PM2.5/1/10-M-D Particulate Matter Sensor with Display – RS485 Modbus: another version this guide coversWittelb WIN-SN-PM2.5/1/10-M-D Particulate Matter Sensor with Display – RS485 Modbus₹7,075
Renke RS-YG-N01 RS485 Photoelectric Smoke Sensor – Modbus-RTU, 10-30V DC: another version this guide coversRenke RS-YG-N01 RS485 Photoelectric Smoke Sensor – Modbus-RTU, 10-30V DC₹7,179
SN-3000-YG2-N01 Smoke Sensor – RS485 Modbus-RTU, 12/24V DC: another version this guide coversSN-3000-YG2-N01 Smoke Sensor – RS485 Modbus-RTU, 12/24V DC₹6,089
JXBS3001-ZXYY-RS Oil Smoke Sensor – RS485 Modbus: another version this guide coversJXBS3001-ZXYY-RS Oil Smoke Sensor – RS485 Modbus₹4,289
PST-YG400A Tuya Smart WiFi Smoke Sensor – 2.4GHz, 20m² Coverage, AAA Battery: another version this guide coversPST-YG400A Tuya Smart WiFi Smoke Sensor – 2.4GHz, 20m² Coverage, AAA Battery₹1,049- USB to RS485 converter: to test Modbus sensors from a PCFind this part
Alternatives and when to choose them
- RS485 temperature and humidity sensor: same bus, other readings.
- PM2.5 dust sensors: module types for DIY.
- Laser PM sensors: bare sensors.
Common mistakes to avoid
- Using it as a fire alarm.
- Duplicate addresses.
- No shelter outdoors.
- Blocked inlets.
Frequently asked questions
How do I read an RS485 PM sensor with ESP32?
Use an RS485 module and a Modbus library to read the registers.
Are these sensors certified smoke alarms?
No. Use certified fire and smoke alarms wherever life safety depends on it.
Why do readings rise in fog?
Fog and mist droplets are counted as particles, so PM readings rise.
How many sensors can share a bus?
Many, as long as each has a unique address.
How often should I clean it?
Clean the inlet every few months, and more often on dusty sites.
Parts for this guide
Keep learning
Sources
Written by the Geekobot team from manufacturer datasheets. Always check the datasheet for the exact part and variant you buy.