Component guide · Intermediate · 3 min read
Water Leak and Immersion Sensors

Renke RS-SJ-N01, SN-3002-SJ, SN-3005-SJ Photoelectric, SN-3006H Rail-Mount and AVATTO ZWS16 Zigbee Leak Detector
By Geekobot Learning Team · Updated 29 Oct 2026
On this page
Leak sensors raise an alarm when water touches the floor under a tank, AC unit, server rack or pump. Industrial types like the Renke RS-SJ give both an RS485 Modbus reading and a relay output to sound a buzzer or stop a pump. The SN-3005 uses an optical probe, and the AVATTO ZWS16 is a battery Zigbee sensor for smart homes.
Key specs at a glance
- Detection
- Electrode probes or optical prism
- Outputs
- RS485 Modbus RTU and relay on industrial types
- Supply
- 10-30V DC typical (industrial); battery (Zigbee)
- Mounting
- Wall box or DIN rail, probe on the floor
- Zigbee
- ZWS16 pairs with a Zigbee 3.0 hub
- Use
- Server rooms, pump rooms, under tanks and AC units
Models in this guide
These are alternatives. Pick the one that fits your project; you only need one.
Option 1Renke RS-SJ-N01-2 Industrial Water Leak Sensor – RS485 Modbus & Relay Output₹4,309
Option 2SN-3002-SJ-N01 King Shell Water Immersion Sensor – RS485 Modbus & Relay Output₹1,849
Option 3SN-3005-SJ-NO1 Photoelectric Water Sensor – RS485 Modbus & Relay Output, IP68₹1,879
Option 4SN-3006H-SJ-NO1 Rail Housing Water Immersion Sensor with Knob – RS485 & Relay Output₹1,709
Option 5AVATTO ZWS16 Water Level Sensor – Zigbee Wireless Water Leak Detector₹749
What the Water leak and immersion sensors (RS485, relay and Zigbee) is
Water leak sensors detect water on floors or near pipes with exposed probes or sensing cables, and raise an alarm or close a valve, often over Zigbee, Wi-Fi or a relay output.
Place the probe at the lowest point of the floor where water would collect first. Use the relay output for a local alarm or to cut a pump, and RS485 to report to a PLC or monitoring system.
Optical probes are not fooled by dirt films on electrodes but must be kept clean. For homes, the Zigbee sensor sends a phone alert through a hub such as a Zigbee dongle.
Water leak and immersion sensors (RS485, relay and Zigbee) pinout
The pins on the Water leak and immersion sensors (RS485, relay and Zigbee) and what each one does.
| Pin | Function |
|---|---|
| Brown or red | +V supply, 5-30V or 12-24V DC |
| Black | 0V |
| Yellow or green | RS485 A (D+) |
| Blue or white | RS485 B (D-) |
| Shield | Earth at one end only |
- Brown or red
- +V supply, 5-30V or 12-24V DC
- Black
- 0V
- Yellow or green
- RS485 A (D+)
- Blue or white
- RS485 B (D-)
- Shield
- Earth at one end only
Wiring the Water leak and immersion sensors (RS485, relay and Zigbee)
Run the probe cable so it cannot be tripped over, and test with a cup of water after installing.
| Water leak and immersion sensors (RS485, relay and Zigbee) pin | Connection | Note |
|---|---|---|
| +V | 12 or 24V DC supply | Check the label |
| 0V | Supply 0V | Common with the converter GND |
| A | Converter A / D+ | Twisted pair |
| B | Converter B / D- | Terminate long runs with 120 ohm |
- +V
- Connection:
- 12 or 24V DC supply
- Note:
- Check the label
- 0V
- Connection:
- Supply 0V
- Note:
- Common with the converter GND
- A
- Connection:
- Converter A / D+
- Note:
- Twisted pair
- B
- Connection:
- Converter B / D-
- Note:
- Terminate long runs with 120 ohm
Example code
Register addresses, decimals and default baud differ by maker. Check the sensor's Modbus table before trusting a value.
# pip install minimalmodbus
import minimalmodbus, time
s = minimalmodbus.Instrument("/dev/ttyUSB0", 1) # COM3 on Windows, slave address 1
s.serial.baudrate = 4800 # many Renke-style sensors ship at 4800; others use 9600
s.serial.timeout = 1
while True:
raw = s.read_register(0, 2) # register 0 with 2 decimals; see the sensor's register map
print("Reading:", raw)
time.sleep(2)Setup and tuning
put sensors at the lowest point near washing machines, water heaters, tanks and under sinks.
pair Zigbee or Wi-Fi versions with your hub or app and test with a damp cloth.
read a probe module with a digital pin; power the probe only when reading to avoid corrosion.
use the alarm to close a motorised valve through a relay.
check battery level in the app regularly.
What you need
Shop this list5 of 7 found in our store · ₹10,495
Renke RS-SJ-N01-2 Industrial Water Leak Sensor – RS485 Modbus & Relay Output: the part this guide coversRenke RS-SJ-N01-2 Industrial Water Leak Sensor – RS485 Modbus & Relay Output₹4,309
SN-3002-SJ-N01 King Shell Water Immersion Sensor – RS485 Modbus & Relay Output: another version this guide coversSN-3002-SJ-N01 King Shell Water Immersion Sensor – RS485 Modbus & Relay Output₹1,849
SN-3005-SJ-NO1 Photoelectric Water Sensor – RS485 Modbus & Relay Output, IP68: another version this guide coversSN-3005-SJ-NO1 Photoelectric Water Sensor – RS485 Modbus & Relay Output, IP68₹1,879
SN-3006H-SJ-NO1 Rail Housing Water Immersion Sensor with Knob – RS485 & Relay Output: another version this guide coversSN-3006H-SJ-NO1 Rail Housing Water Immersion Sensor with Knob – RS485 & Relay Output₹1,709
AVATTO ZWS16 Water Level Sensor – Zigbee Wireless Water Leak Detector: another version this guide coversAVATTO ZWS16 Water Level Sensor – Zigbee Wireless Water Leak Detector₹749- USB to RS485 converter: to read Modbus sensors from a PCFind this part
- 24V switching power supply board: to power 12-24V industrial sensors on the benchFind this part
Alternatives and when to choose them
- RS485 water quality sensors: measure the water itself.
- Sonoff Zigbee dongle: a hub for Zigbee sensors.
- Float level switch: tank level.
Common mistakes to avoid
- Mounting the sensor above floor level.
- Never testing the alarm.
- Leaving probes powered all the time.
- Ignoring low battery alerts.
Frequently asked questions
Where should I place water leak sensors?
At the lowest spots near washing machines, geysers, tanks and under sinks.
Can a leak sensor shut off the water?
Yes, if it drives a motorised valve through a hub automation or relay.
How do I test a leak sensor?
Touch the probes with a damp cloth and check that the alert arrives.
Why does my DIY probe corrode?
Constant current through water causes electrolysis; power it only when reading.
Can it detect slow drips?
Only once water reaches the probes, so place them where drips collect.
Parts for this guide
Keep learning
Sources
Written by the Geekobot team from manufacturer datasheets. Always check the datasheet for the exact part and variant you buy.