Uses the IEC 60751 Callendar–Van Dusen equation. A 2-wire probe adds its lead resistance to the reading, so measure it (short the probe end) and enter it, or use a 3-wire or 4-wire amplifier such as the MAX31865.
t ≥ 0 °C: R = R0 × (1 + A·t + B·t²)t < 0 °C: R = R0 × (1 + A·t + B·t² + C·(t − 100)·t³)A = 3.9083×10⁻³, B = −5.775×10⁻⁷, C = −4.183×10⁻¹²t = (−A + √(A² − 4B(1 − R/R0))) ÷ 2BA PT100 reading 119.40 Ω is 50.0 °C. At 100 °C it reads 138.51 Ω, and at 0 °C exactly 100 Ω. A PT1000 gives ten times the resistance at every temperature.
Platinum resistance thermometers (PT100 and PT1000) are the standard industrial temperature sensors: accurate, stable and nearly linear from −200 °C to 850 °C. Their resistance rises by about 0.385 Ω per °C for a PT100.
Because a PT100 changes so little per degree, lead resistance matters: 1 Ω of cable adds roughly 2.6 °C of error. Use 3-wire or 4-wire probes with a dedicated amplifier such as the MAX31865, or choose a PT1000 whose bigger signal is ten times less sensitive to the same cable resistance.
Both are platinum sensors with the same curve. A PT100 reads 100 Ω at 0 °C and a PT1000 reads 1000 Ω, so the PT1000 gives ten times the signal and is far less affected by cable resistance.
The two lead wires add resistance in series with the sensor, and each ohm looks like about 2.6 °C. Measure the lead resistance and subtract it, or use a 3-wire or 4-wire connection.
About 138.5 Ω, from 100 Ω at 0 °C.
t ≥ 0 °C: R = R0 × (1 + A·t + B·t²); t.
A PT100 reading 119.40 Ω is 50.0 °C. At 100 °C it reads 138.51 Ω, and at 0 °C exactly 100 Ω. A PT1000 gives ten times the resistance at every temperature.
Geekobot builds that use it include Warm box for dough and yoghurt with a PTC heater and a safety cut-out. Each has the full parts list, wiring and code.
Results are estimates for design and learning. Check critical designs against the component datasheet. Made by the Geekobot Learning Team. How we write our calculators