How-to · Intermediate · 3 min read
4-20 mA and 0-10 V Signals
Transmitters, Converters and Reading Them with Arduino and ESP32
By Geekobot Learning Team · Updated 29 Oct 2026
On this page
A 4-20 mA loop sends a measurement as current, so it works over long, noisy cables and a broken wire shows as 0 mA. Power the loop (often 24 V), put a precise shunt resistor (250 Ω gives 1 to 5 V) in series and read the voltage with an ADC. A 0-10 V signal needs a voltage divider before a 3.3 V or 5 V input. Isolate where ground loops are likely.
Key specs at a glance
- Current loop
- 4 mA = zero, 20 mA = full scale
- Voltage
- 0-10 V or 1-5 V
- Shunt
- 250 Ω gives 1-5 V; use a 0.1% resistor
- Supply
- Typically 24 V DC for loop power
- Converters
- ADC modules, PWM-to-voltage DAC, RS485 converters
- Isolation
- Recommended for long runs
Why 4-20 mA
Current signals are not affected by cable resistance or most noise, so they work over hundreds of metres. The 4 mA base (a live zero) lets the system tell a sensor reading of zero from a broken wire. Most industrial level, pressure and temperature transmitters use it; see pressure transducers and industrial flow meters.
2-wire, 3-wire and 4-wire
The wiring depends on how the device is powered.
| Type | Wires | Power |
|---|---|---|
| 2-wire loop-powered | 2 | Loop supply provides power and carries the signal |
| 3-wire | 3 | Separate power, shared return |
| 4-wire | 4 | Separate power; active output |
- 2-wire loop-powered
- Wires:
- 2
- Power:
- Loop supply provides power and carries the signal
- 3-wire
- Wires:
- 3
- Power:
- Separate power, shared return
- 4-wire
- Wires:
- 4
- Power:
- Separate power; active output
Reading 4-20 mA with a microcontroller
1. Connect the 24 V supply, the transmitter and a 250 Ω resistor in series. 2. Measure across the resistor; 4 mA gives 1 V and 20 mA gives 5 V. 3. For a 3.3 V ADC use a 150 Ω shunt (0.6 to 3 V) or divide the voltage. 4. Use a precise 16-bit ADC such as the ADS1115 for accuracy; see ADC basics. 5. Scale the reading to engineering units and flag anything under 3.6 mA as a fault. Use the shunt resistor tool to check values and power.
Reading and creating 0-10 V
0-10 V outputs are common on PLC sensors and HVAC. Divide the voltage down to the ADC range with precision resistors (see the voltage divider tool). To produce 0-10 V from a microcontroller, use a DAC module with an op-amp gain stage; a PWM-to-voltage DAC such as the GP8501 outputs up to its supply and needs amplification for 10 V. See ADC and DAC modules and op-amps.
Digital alternatives
Many modern transmitters, such as pH controllers, flow gauges and vacuum gauges, offer RS485 Modbus instead; see Modbus with Arduino and ESP32 and RS485. Keep 4-20 mA wiring away from mains and use shielded twisted pair.
Try it: Current shunt resistor calculator
Change the values and the diagram and results update as you type.
Common mistakes to avoid
- Connecting a 4-20 mA transmitter straight to an ADC input.
- Using a loose-tolerance shunt resistor.
- Ignoring that 0 mA means a fault.
- Overloading a 3.3 V input with a 5 V signal.
- Running signal wires beside mains cables.
Frequently asked questions
Why is the minimum 4 mA?
So that a broken wire (0 mA) can be told apart from a zero reading.
What resistor do I use?
250 Ω for 1-5 V or 150 Ω for a 3.3 V ADC.
Can I power the transmitter from 5 V?
Most need 12 to 24 V.
How do I convert 0-10 V to 3.3 V?
Use a voltage divider.
Should I use isolation?
Yes in noisy sites or when grounds differ.