A PT100 is a platinum resistor that measures 100 ohms at 0 °C and rises in a very repeatable way with temperature. It is more accurate and stable than thermistors or thermocouples in the range of about -50 to 400 °C. Read it with a MAX31865 amplifier over SPI, use 3-wire or 4-wire connections on long cables and pick Class A parts for the best accuracy.
Key specs at a glance
- Element
- Platinum; 100 Ω (PT100) or 1000 Ω (PT1000) at 0 °C
- Coefficient
- 0.00385 Ω/Ω/°C (IEC 60751)
- Tolerance
- Class A ±(0.15 + 0.002|t|) °C; Class B wider
- Range
- About -50 to 400 °C for common probes; higher for ceramic types
- Wiring
- 2, 3 or 4 wire
- Reader
- MAX31865 (SPI) or a transmitter 4-20 mA
Why choose an RTD
Thermistors are cheap but non-linear and drift. Thermocouples cover very high temperatures but are less accurate. A PT100 is stable and nearly linear, so it is the standard for laboratory, food, HVAC and process measurements. See NTC thermistors and choosing a temperature sensor for comparisons.
2, 3 or 4-wire connections
The cable resistance adds to the measurement. Use the connection that matches your accuracy.
| Wiring | Accuracy | Use |
|---|---|---|
| 2-wire | Lowest; cable adds error | Short leads only |
| 3-wire | Cancels most lead resistance | Industrial standard |
| 4-wire | Cancels all lead resistance | Laboratory accuracy |
- 2-wire
- Accuracy:
- Lowest; cable adds error
- Use:
- Short leads only
- 3-wire
- Accuracy:
- Cancels most lead resistance
- Use:
- Industrial standard
- 4-wire
- Accuracy:
- Cancels all lead resistance
- Use:
- Laboratory accuracy
Reading with a MAX31865
The MAX31865 amplifier measures the resistance and gives a 15-bit value over SPI. Set the jumpers for 2, 3 or 4-wire and the reference resistor (430 Ω for PT100, 4300 Ω for PT1000). Use a library to convert the reading to temperature, and the PT100 calculator to check values. Keep the sensor current small so the element does not self-heat.
Probes, sleeves and mounting
Choose the probe housing for the process: stainless steel for liquids, a flange type for ovens, or a duct sensor for air. A protective sleeve (thermowell) lets you remove the probe without draining a tank. Insert the probe deep enough that the element sits in the flow, and use thermal paste in dry wells. Allow time to settle, since large probes respond slowly.
Calibration
Check the probe in an ice bath (0 °C) and, if possible, in boiling water corrected for altitude. Store an offset if the reading is off. Class A and 4-wire give a good start, but re-check yearly in critical work.
Try it: Pt100 rtd calculator
Change the values and the diagram and results update as you type.
Common mistakes to avoid
- Using a 2-wire connection on a long cable.
- Setting the wrong reference resistor on the MAX31865.
- Mixing PT100 and PT1000 settings.
- Ignoring self-heating from high current.
- Leaving the probe too short in a well.
Frequently asked questions
PT100 or PT1000?
PT1000 has higher resistance, so lead errors are smaller. PT100 is more common in industry.
Is a PT100 better than a thermocouple?
It is more accurate up to about 400 °C. Thermocouples go much higher.
What does Class A mean?
A tighter tolerance than Class B.
Can I read a PT100 with an Arduino ADC?
Poorly. Use a MAX31865 or an analog front end.
Do I need 4-wire?
Only for the highest accuracy.
Parts for this guide
Calculators
Terms in this guide
Projects that use it
Put this into practice: 1 step-by-step build in our project library uses parts from this guide.
Keep learning
Sources
Written by the Geekobot team from manufacturer datasheets. Always check the datasheet for the exact part and variant you buy.