Component guide · Intermediate · 4 min read
Wittelb WIN-IO Modbus Modules

Analog In, Analog Out, RTD and Mixed IO
By Geekobot Learning Team · Updated 29 Oct 2026
On this page
Wittelb WIN-IO modules are Indian-made Modbus IO blocks for panels and data loggers. The 4AIM and 8AIM read 4 to 20 mA or voltage signals, the 4AOMC and 4AOMV drive current or voltage outputs, the 2PT2THM reads RTDs and thermocouples, and the mixed modules combine digital and analog IO. RS485 models use Modbus RTU; the E models speak Modbus TCP and MQTT over Ethernet.
Key specs at a glance
- Interfaces
- RS485 Modbus RTU; Ethernet Modbus TCP and MQTT on E/TCP models
- Analog inputs
- 4 or 8 channels, 4 to 20 mA or voltage, 12-bit
- Analog outputs
- 4 channels, 4 to 20 mA (AOMC) or 0 to 10 V (AOMV)
- Temperature
- 2 RTD plus 2 thermocouple channels (2PT2THM)
- Mixed IO
- 4DI/3DO/4AI/2AO and 8DI/8DO versions
- Supply
- 12 to 24 V DC typical
Models in this guide
These are alternatives. Pick the one that fits your project; you only need one.
Option 1Wittelb WIN-IO-4AIM 4-Port Analog Input to Modbus RS485 Converter (12-Bit)₹6,293
Option 2Wittelb WIN-IO-8AIM 8-Port Analog Input to Modbus RS485 Converter₹7,473
Option 3Wittelb WIN-IO-4AOMC 4-Port Analog Output to Modbus RS485 Converter₹6,555
Option 4Wittelb WIN-IO-4AOMV 4-Port Analog Output Voltage to Modbus RS485 Converter₹6,424
Option 5Wittelb WIN-IO-4DI3DO4AI2AOM I/O Module, 4DI/3DO/4AI/2AO, Modbus RS485₹7,604
Option 6Wittelb WIN-IO-4DDAI-NTCM RS485 Modbus I/O Module₹7,211
What the Wittelb WIN-IO Modbus module is
Each module is a Modbus slave with a configurable address and baud rate. A PLC, HMI, SCADA PC, Raspberry Pi or Wittelb's own 4G gateway polls it and gets engineering values from holding registers.
The Ethernet models can push values to an MQTT broker on their own, which removes the need for a separate gateway in small systems.
Wittelb WIN-IO Modbus module pinout
The pins on the Wittelb WIN-IO Modbus module and what each one does.
| Pin | Function |
|---|---|
| A / B / GND | RS485 bus |
| LAN | Ethernet on TCP and MQTT models |
| +V / GND | 12 to 24 V supply |
| AI1 to AI8 | Analog inputs |
| AO1 to AO4 | Analog outputs |
| DI / DO | Digital inputs and outputs |
| RTD / TC | Temperature inputs on 2PT2THM |
- A / B / GND
- RS485 bus
- LAN
- Ethernet on TCP and MQTT models
- +V / GND
- 12 to 24 V supply
- AI1 to AI8
- Analog inputs
- AO1 to AO4
- Analog outputs
- DI / DO
- Digital inputs and outputs
- RTD / TC
- Temperature inputs on 2PT2THM
Wiring the Wittelb WIN-IO Modbus module
Follow the terminal labels on the module: input types (current or voltage) may be set by jumpers or registers. Use shielded cable for analog and RTD signals.
| Wittelb WIN-IO Modbus module pin | RS485 models | Ethernet models |
|---|---|---|
| A / B | Master RS485 A / B | - |
| +V / GND | 24 V supply | - |
| AI (2-wire 4-20 mA) | 24 V to sensor +, sensor - to AI | - |
| LAN | - | Router or switch |
- A / B
- RS485 models:
- Master RS485 A / B
- Ethernet models:
- -
- +V / GND
- RS485 models:
- 24 V supply
- Ethernet models:
- -
- AI (2-wire 4-20 mA)
- RS485 models:
- 24 V to sensor +, sensor - to AI
- Ethernet models:
- -
- LAN
- RS485 models:
- -
- Ethernet models:
- Router or switch
Example code
Register addresses and scaling come from the Wittelb manual for each model. Convert raw counts to mA or engineering units as the manual shows.
import minimalmodbus
m = minimalmodbus.Instrument("/dev/ttyUSB0", 1)
m.serial.baudrate = 9600
for ch in range(8):
raw = m.read_register(ch, functioncode=3)
print("AI", ch + 1, raw)Setup and tuning
set a unique address on each module before connecting them together.
on E models, set broker, topic and interval in the web page.
power two-wire transmitters from 24 V with the module input in the loop.
run A, B and a ground or shield wire; A to A and B to B on every device.
fit 120 ohm resistors only at the two ends of a long bus.
daisy-chain the devices; avoid stars and long stubs.
every device on one bus needs the same baud rate and parity and a unique Modbus address.
What you need
Shop this list13 of 13 found in our store · ₹79,354
Wittelb WIN-IO-4AIM 4-Port Analog Input to Modbus RS485 Converter (12-Bit): the part this guide coversWittelb WIN-IO-4AIM 4-Port Analog Input to Modbus RS485 Converter (12-Bit)₹6,293
Wittelb WIN-IO-8AIM 8-Port Analog Input to Modbus RS485 Converter: another version this guide coversWittelb WIN-IO-8AIM 8-Port Analog Input to Modbus RS485 Converter₹7,473
Wittelb WIN-IO-4AOMC 4-Port Analog Output to Modbus RS485 Converter: another version this guide coversWittelb WIN-IO-4AOMC 4-Port Analog Output to Modbus RS485 Converter₹6,555
Wittelb WIN-IO-4AOMV 4-Port Analog Output Voltage to Modbus RS485 Converter: another version this guide coversWittelb WIN-IO-4AOMV 4-Port Analog Output Voltage to Modbus RS485 Converter₹6,424
Wittelb WIN-IO-4DI3DO4AI2AOM I/O Module, 4DI/3DO/4AI/2AO, Modbus RS485: another version this guide coversWittelb WIN-IO-4DI3DO4AI2AOM I/O Module, 4DI/3DO/4AI/2AO, Modbus RS485₹7,604
Wittelb WIN-IO-4DDAI-NTCM RS485 Modbus I/O Module: another version this guide coversWittelb WIN-IO-4DDAI-NTCM RS485 Modbus I/O Module₹7,211
WIN-IO-2PT2THM 2-Channel RTD & 2-Channel Thermocouple to Modbus RS485 Module: another version this guide coversWIN-IO-2PT2THM 2-Channel RTD & 2-Channel Thermocouple to Modbus RS485 Module₹6,031
Wittelb WIN-IO-4DDAME-MQTT-IO Module w/ 4DI 4DO 4AI Modbus TCP: another version this guide coversWittelb WIN-IO-4DDAME-MQTT-IO Module w/ 4DI 4DO 4AI Modbus TCP₹9,308
Wittelb WIN-IO-8DDME-IO Module 8DI 8DO Modbus TCP: another version this guide coversWittelb WIN-IO-8DDME-IO Module 8DI 8DO Modbus TCP₹10,489
24V 4A switching power supply board: the usual supply for DIN rail devices24V 4A AC-DC Switching Power Supply Board₹411Closest match, check the specs
USB to RS485 converter adapter: to test the bus from a PCUSB to RS485 Converter Adapter₹74
DIN rail screw terminal block: to land field wires neatly on the railDIN Rail Screw Terminal Block₹20
Raspberry Pi 4 Model B 4GB: a small Modbus master or Node-RED hostRaspberry Pi 4 Model B with 4GB RAM₹11,461Closest match, check the specs
Alternatives and when to choose them
- Waveshare Modbus RTU IO modules: 8-channel alternatives.
- RS485 4G MQTT gateways: send module data to the cloud.
- PT100 RTD sensors: the probes for the RTD inputs.
Common mistakes to avoid
- Duplicate addresses on one bus.
- Voltage sensor on an input set for current.
- Thermocouple extension wire of the wrong type.
- Unshielded analog cable next to motor wiring.
Frequently asked questions
Can a PLC read these?
Yes, any Modbus RTU or TCP master can.
Do they support MQTT?
The Ethernet MQTT models do; RS485 models need a gateway.
What resolution are the inputs?
12-bit on the analog input modules.
Can I mix modules on one bus?
Yes, with unique addresses and the same serial settings.
Which module for a pressure transmitter?
A 4AIM or 8AIM with the channel set to 4 to 20 mA.