Single phase: S = V × I, P = S × PFThree phase: S = √3 × V(L-L) × I, P = S × PFQ = S × sin(φ), φ = arccos(PF)Capacitor kVAR = P × (tan φ1 − tan φ2)A single-phase 230 V load drawing 10 A at PF 0.85: S = 2.3 kVA, P = 1.955 kW, Q = 1.21 kVAR. Raising the power factor to 0.95 needs about 0.57 kVAR of capacitors.
In AC circuits, current does not always rise and fall together with voltage. Motors and transformers lag, so the power actually used (kW) is less than the volt-amps (kVA) the supply must deliver. The ratio is the power factor.
A low power factor wastes cable capacity, and commercial electricity bills in India often penalise it. Capacitor banks supply the reactive power locally. Always follow the electrical code and have mains work done by a qualified electrician.
Real power ÷ apparent power, P ÷ S. A motor with PF 0.8 draws 1.25 times more current than its real power suggests.
kVA = kW ÷ power factor. A 4 kW load at PF 0.8 needs 5 kVA.
S = √3 × line voltage × current. At 415 V and 10 A that is about 7.2 kVA.
Single phase: S = V × I, P = S × PF; Three phase: S = √3 × V(L-L) × I, P = S × PF; Q = S × sin(φ), φ = arccos(PF); Capacitor kVAR = P × (tan φ1 − tan φ2).
A single-phase 230 V load drawing 10 A at PF 0.85: S = 2.3 kVA, P = 1.955 kW, Q = 1.21 kVAR. Raising the power factor to 0.95 needs about 0.57 kVAR of capacitors.